CVE-2025-11782Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2.
Updated under an hour ago ()
Does this affect you?
It affects circutor sge-plc1000_firmware and 1 other product. Add what you run to find out whether that includes you.
No exploitation reported and no EPSS estimate yet.
Do this next
Free account, 1 product
Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. The 'ShowDownload()' function uses “sprintf()” to format a string that includes the user-controlled input of 'GetParameter(meter)' in the fixed-size buffer 'acStack_4c' (64 bytes) without checking the length. An attacker can provide an excessively long value for the 'meter' parameter that exceeds the 64-byte buffer size.
- CVSS
- 9.8 CRITICAL (v3.1, NVD)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- Weakness (CWE)
- CWE-121
- Known exploited
- Not in CISA's KEV catalog
- EPSS (exploitation in the next 30 days)
- Not loaded for this CVE
- Assigned by
- Not given
- NVD analysis
- Analyzed
- Record last updated
- Sep 26, 2026
- First seen by InfoSec Signals
- Oct 9, 2026
Affected products
circutor sge-plc1000_firmware circutor:sge-plc1000_firmware | 9.0.2 | NVD |
circutor sge-plc50_firmware circutor:sge-plc50_firmware | 9.0.2 | NVD |
References
- https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0third-party-advisory
The CVE record on cve.org NVD's entry
The CVE record is authoritative. Products marked “from the name” were identified from the CNA's free-text names, not a CPE, and are matched less certainly. This product uses the NVD API but is not endorsed or certified by the NVD.